Cable

DIN EN 50266- part 2-1 (Edition Septembre 2001)

Common test methods for cables under fire conditions
Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-1: Procedures – Category A F/R
This part 2-1 of covers category A F/R and relates only to power cables of conductor cross-sectional area greater than35 qmm installed on the test ladder in a spaced configuration on the front and rear to achieve a nominal total volume of non-metallic material of 7l/m of test sample. The flame application time is 40 min. Category A F/R is not intended for general use.

DIN EN 50266- part 2-2 (Edition Septembre 2001)

Common test methods for cables under fire conditions
Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-2: Procedures – Category A
This part 2-2 of covers category A and relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 7 l/m of test sample. The flame application time is 40 min.
The category is intended for general use where high volumes of non-metallic material are required to be evaluated.

DIN EN 50266- part 2-3 (Edition Septembre 2001)

Common test methods for cables under fire conditions
Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-3: Procedures – Category B
This part 2-3 of covers category B and relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 3,5 l/m of test sample. The flame application time is 40 min. The category is intended for general use where medium volumes of non-metallic material are required to be evaluated.

DIN EN 50266- part 2-4 (Edition Septembre 2001)

Common test methods for cables under fire conditions
Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-4: Procedures – Category C
This part 2-4 of covers category C and relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 1,5 l/m of test sample. The flame application time is 20 min.
The category is intended for general use where low volumes of non-metallic material are required to be evaluated.

DIN EN 50266- part 2-5 (Edition Septembre 2001)

Common test methods for cables under fire conditions
Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-5: Procedures Ð Small cables
– Category D
This part 2-5 of covers category D and relates only to small of overall diameter 12 mm or smaller installed on the test ladder to achieve a nominal total volume of non-metallic material of 0,5 l/m of test sample. The flame application time is 20 min.
The category is intended for use with small cables where very low volumes of non-metallic material are required to be evaluated.

DIN EN 50268 part 1

Measurement of the smoke density of cables and insulated wires during burning under definite conditions; testing device

DIN EN 50268 part 2

Measurement of the smoke density of cables and insulated wires during burning under definite conditions; testing procedure

IEC 61034 part 2

Measurement of smoke density of cables burning under defined conditions

IEC 60332 - part 3-21 (first edition 2000)

Test on electric cables under fire condition Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A F/R

IEC 60332 - part 3-22 (first edition 2000)

Test on electric cables under fire condition Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60332 - part 3-23 (first edition 2000)

Test on electric cables under fire condition Test for vertical flame spread of vertically-mounted bunched wires or cables – Category B

IEC 60332 - part 3-24 (first edition 2000)

Test on electric cables under fire condition Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C

IEC 60332 - part 3-25 (first edition 2000)

Test on electric cables under fire condition Test for vertical flame spread of vertically-mounted bunched wires or cables – Category D

IEC 60332 - part 1-2 (first edition 2004)

Test on electric and optical fibre cables under fire condition - Test for vertical flame propagation for a single insulated wire or cables – Procedure for 1 kW pre-mixed flame

DIN EN 60332-1-2 (edition June 2005)

Test on electric and optical fibre cables under fire condition Test for vertical flame propagation for a single insulated wire or cables – Procedure for 1 kW pre-mixed flame

IEC 60331 - 21 (first edition 1999)

Test for electric cables under fire condition –
Circuit integrity –
Procedures and requirements –
Cables of rated voltage up to and including 0,6/1,0 kV 